Recherche avancée
recherches apparentées: Bluetooth, Virtual Reality, android, smart phone, mtk, smart watch, Keyboard, OPENBOX Voir tous
Image de SKG-V1-6KVA HF UPS

SKG-V1-6KVA HF UPS

SKU: FS00019487
Reproduction is welcome and allowed for free circulation only.
     
Main Features
APPLICATION:
small network servers and other IT equipment
Features and Benefits
●High frequency and double conversion on-line technology
●Intelligent MCU control
●Wide input voltage range
●UPS start up without battery
●Cold start
●Advanced battery management
●Automatic battery charge in UPS off mode
●Lightning and surge protection
●Short circuit and overload protection
●Fan speed auto control when loads varies
●Optional extension battery pack
●EMI/RFI noise filter
●Smart RS232,USB,RJ45 communication with monitoring software
●Optional SNMP Card slot
●with LCD and LED two type front panel
●In LCD model, nominal bypass ECO setting function
●In LCD model, Generator setting function
●In LCD model, Output voltage 220V,230V,240V setting function
●EPO control system option
Overview
Model

SKG-V1K

SKG-V1KS

SKG-V2K

SKG-V2KS

SKG-V3K

SKG-V3KS

SKG-V4K

SKG-V4KS

SKG-V6K

SKG-V6KS

Specifications

Capacity(VA/W)

1000VA/700W

2000VA/1400W

3000VA/2100W

4000VA/2800W

6000VA/4200W

INPUT Feature

Battery voltage(Vdc)

24

48

96

120

144

Voltage Range(Vac)

176~286VAC @ full load (138~300VAC @ half load)

Frequency Range(Hz)

46 ~ 54Hz / 56 ~ 64Hz

Number of phases

single phase&earth ground

Power Fator

≥0.98, Full RCD Load

Generator Input

Support

Output feature

Voltage

220/230/240VAC± 1%

Frequency ( Battery Mode )

50/60Hz ± 0.1 Hz

Frequency(Hz)

50±0.2% (battery mode)

Wave form

Pure Sine wave THD<4%

Overload Capacity(Line Mode)

>=110%; 2mins, Then transfer to bypass and Alarm, >=150%; 10 S, Then transfer to bypass, turn off output after 1mins and Alarm

Overload capacity( Battery Mode )

> =110 %; 30 S, Then turnoff output and Alarm,> =120 %; 1S, Then turnoff output and Alarm

Output mode

IEC x2

IEC x4

IEC x4

Terminal Block

Terminal Block

Battery

Battery Type

12V/9AH

Depending on the capacity of external batteries

12V/9AH

Depending on the capacity of external batteries

12V/5AH

Depending on the capacity of external batteries

12V/4.5AH

Depending on the capacity of external batteries

12V/9AH

Depending on the capacity of external batteries

Numbers of Batteries

2

4

8

10

12

Backup Time (Half Load)

>10 min

>10 min

>10 min

>10 min

>12 min

Recharge Time (to 90%)

5 Hours

5 Hours

3Hours

3 Hours

3Hours

Charging Current (Max.)

1.0A

3.0A

1.0A

3.0A

2.0A

6.0A

2.0A

6.0A

2.0A

6.0A

Rated Charging Voltage

26.9~27.9vdc

53.6~55.5vdc

108~111vdc

134 ~137Vdc

161 ~164Vdc

Other feature

EFFICIENCY(AC /Battery Mode)

93%-92%

TRANSFER TIME(AC to DC)

Zero

TRANSFER TIME(Inverter to Bypass)

4ms (Typical )

AUDIBLE ALARM(Battery Mode)

Sounding every 4 seconds

INDICATOR(LED Version)

Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault

INDICATOR(LCD Version)

Load / Battery / Input / Output / Operating Mode Information

Protections

Low battery protection,overload protection,short-circuit protection,overheated protection

Ambient temperes

0℃-40℃

Reative humidity

0-95% no condensation

ProductsSize(mm)

145×220×355

190×318×383

190×318×433

260×483×573

260×570×717

Products Weight(KG)

12

5.2

23

10.8

25

12

75

28

90

35